Product description: SafeHAUS SHG-01 Natural Gas Sensor - 230 V
The SHG-01 sensorby SAFEHAUS is designed to monitor rooms for escaping natural gas. It is powered by 230 V. The sensor has a certificate confirming that it meets the requirements of the Polish standard EN50194-1:2009, whichallows it to be installed not only in homes but also in commercial and service premises. In case of gas detectionan optical-acoustic alarmis activated.
SAFEHAUS SHG-01 natural gas sensor.
Installation of SafeHAUS SHG-01 natural gas sensor - 230 V
As the gas from the gas installation is lighter than air in the event of a leak, it starts to collect under the ceiling and fill the room from above, so the sensor should be installed about 30 cm from the ceiling in a place where air movement will not be disturbed. Also make sure not to installthe sensor:
- Directly above kitchen appliances (gas stove, cooker, burner, etc.).
- In external areas
- In an enclosed space (e.g. a loose cabinet behind a curtain)
- Directly above the sink and in humid places
- Next to doors and windows
- Next to the exhaust fan or hood
- In places where the temperature may fall below -10 °C or exceed 40 °C
- In places where dirt and dust can clog the device
The table below shows the operating status of the device and the status of the notifications that occur.
Status | Description |
Green POWER LED |
Yellow FAULT diode |
Red ALARM diode |
Beacon audio |
---|---|---|---|---|---|
Auto test |
Power on | It lights up . | It lights up . | It lights up . | 1 beep |
Warming up |
Approximately 180 seconds after start-up | Blinks 0.5 s / 1 s | It doesn't shine | It doesn't shine | Excluded |
Vigil |
Normal work | Lights steady | It doesn't shine | It doesn't shine | Excluded |
Test |
Testing the device after pressing TEST/HUSH button |
Lights steady | It doesn't shine | Blinks 0.5 s / 1 s | ALARM diode spades |
ALARM |
The device detected the gas | Lights steady | It doesn't shine | Blinks 0.5 s / 1 s | ALARM diode spades |
Mute |
Press the TEST/HUSH button during the alarm |
Lights steady | It doesn't shine | Blinks 0.5 s / 1 s | Excluded |
Sensor malfunction |
Contact the service | Lights steady | Lights steady | It doesn't shine | 1 beep every 30 seconds |
Special functions |
The device should swap for new ones |
Lights steady | Lights steady | It doesn't shine | 3 beep every 30 seconds |
Memory Embedded |
The power cable is disconnected | It doesn't shine | It doesn't shine | It doesn't shine | Excluded |
If an alarm sounds, be calm and do the following:
- Switch off all gas appliances
- Open doors and windows to increase ventilation
- Do not turn on or off any electrical devices, including gas detectors
- Switch off the gas supply by shutting off the main valve in the building
- Do not use the phone in a gas room
- Contact the gas service or its supplier
Attention! Before connecting, please read the supplied manual. After connecting the power supply the sensor needs about 3 minutes for calibration. |
We also offer otheralarmsensors.
SAFEHAUS SHG-01 - 230 V natural gas sensor specification
- Power supply: 230 V AC
- Sensor type: solid-state
- Detects: natural gas / methane
- Certificate of conformity to EN50194-1:2009 issued by BSI
- Sensitivity: 6% DGW (Lower Explosion Limit)
- Volume: >85 dB at 1 meter distance
- Energy consumption:< 4 W
- Operating temperature: -10 °C to 40 °C
- Operating humidity: 0 to 95 % RH
- Dimensions: 117 x 77 x 36 mm